Contact Us Contact Us

HP Modular Cooling System G2 Firmware

  Software Depot
Electronic download
Frequently asked questions
Product details & specifications
Receive for Free
Overview

The MCSG2 could potentially display an erroneous "water valve failed" alarm when the unit is run very close to the low end of the valid operating parameters. In particular if the unit is run with a low heat load, very cold water and high water flow rate, which provides much more cooling capacity than is required and is very energy inefficient. Running the MCSG2 under this condition can cause excessive opening and closing of the chilled water valve which would generate the erroneous alarm.

 
Additional product information
Product #: AF025A
Version: 2.3.03
Software specification: HP Modular Cooling System G2 Firmware (AF025-10503.zip)